Str. Dr. Louis Pasteur nr. 8, sector 5, 050535, Bucuresti, Romania 0214103182 0214103064 [email protected]

Battery Monitoring CELLGUARD™ Wired

Print
Manufacturer: Franklin-Electric show products
Hits: 349

 Description

ENSURE UPTIME WITH 24/7 MONITORING

Utility personnel are provided with continuous 24/7 monitoring of key battery performance indicators to help enable proactive maintenance, ensure battery performance, and deliver uninterrupted uptime when it matters the most.

KEY ADVANTAGES

 
STATE OF HEALTH - The BMS helps analyze data trends related to battery state of health, simplifying the detection of potential issues for operators to optimize battery usage.
INTERNAL RESISTANCE TESTING AND PERFORMANCE TRENDING - The BMS tests a given battery’s internal resistance at a pre-determined interval. The results are then collected and presented as a trend providing the user with genuine DC power plant performance insight.
DISCHARGE EVENTS - Battery discharge events are recorded automatically (including battery voltage, string voltage, discharge current and discharge capacity).
PARAMETER AND ALARM THRESHOLDS - The user can set / modify many measurement parameters and thresholds either locally or remotely. The system invokes a permission hierarchy to manage administrative access.
 

1. Control Module

2. Battery Sensor Module

3. String Sensor Module

4. Current Transducer

6. CELLTRAQ Data Management Software

Specifications

Environmental Measurements

  • Operating temperature: -10°C to 50°C
  • Humidity: 5% to 95%

Monitoring Capability

  • Maximum batteries on a single String: 180
  • Control module string maximum: 6
  • Control module battery maximum: 360

Include 1 Relay and 2 Dry Contact Inputs

Specifications

  • Battery types: 2V, 6V, 12V (capacity less than 3000AH)
  • Insulation: 2000 VAC
  • Weight (Coordinator): 0.3 Kg
  • Weight (Battery Sensor): 75 g
  • Weight (String Sensor): 80 g

Controller Module Communication Interfaces

  • Serial Comm. Port: RS485 Modbus/RTU
  • RJ45 Ethernet Comm. Port: SNMP, Modbus/TCP
  • RJ22 Module Comm. Port: COM1-COM3 UART

Power Requirements

  • Base coordinator unit: 14-36 VDC 40W, external power supplies available
  • Battery sensor: < 13mA (1.2V, 2V) or 7mA (6V, 12V) from battery
  • String sensor: 10.8 to 13.8VDC, 2W, power from control module

Approvals & Certifications

  • EMC Certification: CISPR 11, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-11
  • Compliance: CE & FCC

Reliability

  • Auto reboot trigger: Build-in WDT
  • MTBF: 100,000 hours

Measurement & Accuracy

Component Range Accuracy
String Voltage 20 to 800V +/- 0.5%
Battery voltage 2V, 6V, 12V +/- 0.1%
Battery resistance 50 to 65535uΏ +/- 2%, 1uΏ
Battery temperature -5°C to 99.9°C +/- 1°C
String current 0 to 1000A +/- 2%
Ambient temperature -5°C to 99.9°C +/- 1°C
Ask about this product

Login