 Description

EXTEND THE LIFE OF YOUR CIRCUIT BREAKER

With early detection of circuit breaker deficiencies and automated system performance evaluation, the Optimizer3 Circuit Breaker Monitor provides utilities with the tools to help improve efficiency, extend equipment service life, and enhance reliability of their systems.

Key Advantages

  • 24/7 REAL-TIME ANALYSIS - The web-based software provides monitoring data on both the mechanical and electrical performance of a circuit breaker, delivering trending analysis that predicts the date of future service. All data can be seamlessly fed into existing back-office software via DNP3 network communication protocol.
  • CONDITION BASED MAINTENANCE - Armed with a high degree of circuit breaker performance insight from the Optimizer3, utilities can deploy maintenance with intelligence and only as needed – limiting truck roles, speeding reaction time, and lowering overall maintenance costs.
  • BREAKER TIMING - In the milliseconds it takes for a circuit breaker to trip, the Optimizer3 collects a full battery of timing data including opening (trip) time, clearing time, arc duration, and opening/closing travel times and velocities are automatically analyzed to provide a full assessment of the circuit breaker’s health.
  • SF6 REPORTING - The Optimizer3 aids in the mandatory compliance reporting required by the EPA, resources boards, and other regulatory agencies by monitoring for SF6 gas leaks and related indicators and automatically reporting any fugitive emissions.
  •  COMPLETE CIRCUIT BREAKER DIAGNOSTICS - With 8 sensor inputs, 5 timing inputs, and an onboard ambient temperature sensor and supply voltage monitor, the Optimzer3 and its array of sensors deliver a complete diagnostics report of a circuit breaker’s performance. Utility technicians are empowered with the data to repair a small issue before it causes a substantial failure that may require equipment replacement or even an entire overhaul of a high-cost asset.
  • .
  • VOLTAGE & CURRENT MONITORING - Real-time voltage and current are measured with an array of high-accuracy, loop-powered voltage and current transducers. Applications include motor current, station battery voltage, heater current, and compressor run-time.​
  • SF6 GAS MONITORING - SF6 gas density, pressure, and dew point sensors and fill point adapters aid in the mandatory compliance reporting required by the EPA, resources boards, and other regulatory agencies by monitoring for SF6 gas leaks and related indicators and automatically reporting any fugitive emissions.
  • SF6 GAS HUMIDITY ABSORBER - The SF6 gas humidity absorber is capable of passively absorbing up to 40 milliliters of water from SF6 gas, saving major expense compared to standard circuit breaker moisture removal. The corrosion-resistant absorber is easily connected to a circuit breaker's SF6 gas port.
  • TANK HEATER MONITORING - The Optimizer3 monitors the tank heater’s supply current using a universal power status monitor. If one or more of the heater elements fails, the Optimizer3 will assert a heater alarm.
  • REMOTE WEB INTERFACE - The web-based interface allows users to securely connect directly to the Optimizer3 monitoring and alarm data from any web-enabled device without having to host anything on a server.
  • DATA COMMUNICATION - Performance data is delivered through standard network communication protocols to maintenance, reliability, and environmental protection stakeholders with role-based access and permissions.
  • SETUP & CONFIGURATION - Remotely setup and program, clear and reset alarms, install firmware upgrades. Personnel can also save, download and copy configurations between breakers.
  • REPORTING - Circuit breaker performance and SF6 gas compliance reports for regulatory agencies can be easily generated and exports in CSV format.  
  • ONCE THE PRODUCT SHIPS, WE'RE JUST GETTING STARTED
Included in package
1. Power input & relay output
2. CT inputs
3. Timing inputs
4. RS-485 ports
5. Digital/analog sensor inputs
6. Analog sensor inputs
7. Status LEDs
8. Mini USB port5678
9. Ambient temperature sensor
10. Fiber-optic port (optional)
11. USB 2.0 port
12. Ethernet port
13. Vents
14. Mounting holes
Specifications Circuit Breaker Monitoring Capabilities
  • Breaker State (Open/Closed)
  • Breaker Timing
  • - Opening & Closing Time (Latch Time)
  • - Opening & Closing Travel Time
  • - Arc Time
  • - Interrupting Time
  • Opening & Closing Travel Velocity
  • Operations Count
  • - Fault-Interrupt Count
  • - Non-Fault-Interrupt Count
  • Days Since Last Operation
  • Trip & Close Coil Circuit Integrity
  • Charging Motor Current Draw & Run Time
  • Contact Wear & Restrike Detection

Circuit Breaker Monitoring Reporting

  • 2-Hour Current Log (5000 Records – FIFO)
    • Min., Max., & Average Current
  • Event History (5000 Records – FIFO)
    • Opening Coil (1 or 2)
    • Timing Measurements
    • Opening & Closing Velocity
    • Peak Fault Current
    • Alarm Status for Each Operation
    • Contact Wear for Each Operation
    • Accumulated Contact Wear

SF6 Gas Monitoring Capabilities

  • Gas Density
  • Gas Pressure
  • Gas Temperature
  • Leakage Trend & Confidence Level
  • Forecasts Days until Low Gas Alarm

SF6 Gas Monitoring Reporting

  • Daily Average (750 Records – FIFO)
    • Pressure, density, temperature & SF6 mass
  • 2-Hour History Log (5000 Records – FIFO)
    • Pressure, density, temperature

Sensor Types Supported

  • SF6 Gas Density, Temperature, Pressure
  • SF6 Gas Dew Point
  • Generic AC/DC Voltage & Current
  • Generic (Hydraulic, Air) Pressure
  • Generic Temperature
  • Tank Heaters (UPSM-241)
  • Analog: 4-20mA (Loop-Powered)
  • Digital: Frequency/Pulse-Width Modulated

Specifications

Environmental Operating Temperature: -40 to 65° C
Storage Temperature: -40 to 65° C
Humidity: 0 to 95% Non-condensing
Communications RS-485 Full/Half Duplex
Ethernet
Fiber-optic (OM3D-F Model Only)
Relay Output Dry Contact; 1 ea. Form C
Relay Contact Rating N.O: 5 Amps @ 250 VAC or 3 Amps @30 VDC
N.C: 2 Amps @ 250 VAC or 1 Amp @ 30 VDC
Relay Contact Fuses 3.15 A Slow-Blow
Power Supply Input Voltage 110-250 VDC / 90-264 VAC, 50 / 60 Hz
Power Consumption 60VA Maximum
Power Supply Input Fuses 3.15 A Slow-Blow
Aux Input Voltage 0 to 48 - 250 VDC
Aux Input Fuses ¼ A Fast-Blow
Aux Input Impedance 540K Ohms
CT Pickup Coil Input Signal 0 to 5 VAC
Input Sampling Rate 32 Samples per line cycle
Sensor Signal Analog: 4 to 20 mA
Digital: Frequency & Pulse-Width Modulated
Sensor Power 20 VDC @ 25mA Max
Analog Sensor Accuracy +/-1% of Full-Scale Max, +/-0.5% Typ.
Dimensions 280 mm L x 70 mm W x 143 mm H
11" L x 2¾" W x 5 5/8" H
Shipping Weight 6 lbs. (2.25Kg)